2 stage Carrier package unit not cooling. call back?
Автор: Everything HVACR
Загружено: 2023-09-21
Просмотров: 3125
Описание: no Cooling Service Call. this unit was found with a failed condenser motor and a failing blower motor a few months ago. both motors and 2 contactors were replaced along with a low pressure switch, and the coils were cleaned at that time. today, I find major restrictions in both refrigerant circuits, contactors chattering, and one failed. small leak from the cormax on stage 2, but once recovered and weighed, I don't believe there are any other refrigerant leaks. filter driers replaced, and the orifice metering devices do not seem to be restricted at this time.