Brush 12500 kVA transformator
Автор: RODALCO2007
Загружено: 2014-04-29
Просмотров: 54946
Описание:
This transformator was taken out of service because of a on load tapchanger fault.
The pressure build up in the TCOL tank caused the fiber terminal support structure to crack open, and trip the Buch Holtz protection relay.
TX was switched off line to avoid further damage.
What will happen is unsure at this stage.