Problem on cooling and adiabatic humidification / Psychrometry/ Refrigeration and air conditioning
Автор: Edutech Guru Engineering Learning-By Priyanka ma'am
Загружено: 2021-12-27
Просмотров: 568
Описание: The atmospheric air at 40°C dry bulb temperature and 18°C wet bulb temperature is flowing at the rate of 100 m3/min through the space. Water at 18°C is injected into the air stream at the rate of 48kg/h. Determine the specific humidity and enthalpy of leaving air. Also determine dry bulb temperature, wet bulb temperature and relative humidity of leaving air.