Table 2 or Table 4? Ampacity Trap Most Apprentices Fail | CEC 2024
Автор: Current Electrical Code (CEC)
Загружено: 2026-11-08
Просмотров: 117
Описание:
Ampacity for aluminum: CEC 2024 Table 2 vs Table 4 (Rule 4-004), Code Question of the Day #11 ⚡
You're sizing aluminum conductors in a raceway or cable. Which CEC table gives you the ampacity?
A) Table 2
B) Table 5A
C) Table 4
Comment your answer before the reveal 👇
Answer: C, Table 4. Rule 4-004 points you to the base ampacity tables: Table 2 is copper, Table 4 is aluminum (raceway/cable; Tables 1 and 3 cover free air). Tables 5A, 5B and 5C are correction factors (ambient temperature, spacing, more than three conductors). They adjust the number, they're not where you start.
The trap: read the copper table for aluminum wire and the ampacity reads too high, so you undersize the conductor. Wrong table, wrong wire at the panel.
Tip: terminations often limit you to the 75 °C column even with 90 °C insulation. Check the breaker and lug temperature rating (Rule 4-006).
Always check your own code book, local amendments, and your inspection authority. Paraphrased, not the code text. Not legal advice.
New Code Question of the Day every day. Follow so you don't miss tomorrow's.
#CEC2024 #CanadianElectricalCode #Ampacity #Electrician #RedSeal #CodeQuestion #Shorts #CurrentCodeCEC