1794-AENT Flex I/O Communication Module
Автор: AB PLC Test Bench
Загружено: 2018-04-19
Просмотров: 45381
Описание:
How I set up and test the AB Ethernet 10/100 communication module. Using RSLinx and BootP server Ver 2.3
To reset the Series B modules to factory default - power off.
Set the switches to 888.
Power on and wait about a minute.
Power off and set to 999.
Use BootP to access the module and set an address.
Then use RSLinx to confirm that the settings are where you want them for your system.
I will do a video on this in the coming week or so.