Rackmount Solutions: Sizing Portable Air Conditioning Unit
Автор: Rackmount Solutions
Загружено: 2015-12-31
Просмотров: 175317
Описание:
How to Size a Portable AC Unit
Portable Air Conditioning Units for the data center, how do I choose the right size? Well, a simple formula can point you in the appropriate direction. For this formula, you’ll need the square feet of your data center or room, the total watts from your equipment, and the number of active people typically found in the room.
The formula is as follows: (Room SQFT x 20) + (Equipment Watts x 3.14) + (Active People in the room x 400) = Size of the Portable A/C Unit necessary in BTU.
Following the result of BTU from the formula, make sure you consider growth over the next year and if you plan on removing any legacy equipment that might be energy guzzlers.
Rackmount Solutions can certainly help find cooling for a single rack, up to a full scale data center, from 10,000 BTU to 92,000 BTU of cooling capacity. We’re also known for our custom Air-Conditioned Server Racks if you need specific cooling for a single rack.
http://www.rackmountsolutions.net/
[email protected]
Toll Free: (800) 352-6631
Rackmount Solutions is an industry leader in supplying server racks, server cabinets, wall mount racks, network racks, LAN racks, portable rackmount cases and accessory products for the IT/Network professional. We deliver rackmount storage server rack solutions for 19", 23", 24" and 28" wide equipment, as well as PCI Data Security Storage compliant cabinets and racks. We pride ourselves in providing quality customer service. Please call us toll free at (800) 352-6631 and let us know how we can solve your rackmount needs.
Повторяем попытку...
Доступные форматы для скачивания:
Скачать видео
-
Информация по загрузке: