How to use Fluke calibrator model no 754 as mA source -Steps & connection details by IVSR TECHI
Автор: VSR TECH
Загружено: 2021-08-07
Просмотров: 1130
Описание:
How to use Fluke calibrator model no 754 as mA source -Steps & connection details by IVSR TECHI
How to test loop devices
To test the input of a controller, connect the output of the loop calibrator to the input of the controller at the input card. Be careful to connect with the correct polarity—black to negative, red to positive. The HMI (Human Machine Interface) or readout of the controller can be monitored for the correct indication as the mA signal being sourced is changed.
For example, if the 4 to 20 mA signal represents the temperature being measured by a temperature transmitter, with a 4 mA from the loop calibrator applied the HMI or controller if operating correctly will indicate the 0% or lower range temperature value of the transmitter. With the mA signal set to 20 mA, the indicator or HMI should indicate the 100% or upper range value of the transmitter.
What the results mean
Deviations between the expected read out value and the actual value would indicate that the A/D converter of the input card needs adjustment. If there is no value indicated and/or the loop calibrator indicates an open circuit either the input card is defective or the input fuse in the card is open. Check for an open fuse with a digital multimeter set in continuity of resistance measurement. The measured value should be somewhere between 100 and 250 ohms.
I VSR TECH I
We are planning to start the online training classes for the students related to PLC and DCS.Then instrumentation & electrical.Once required contact [email protected].
Thanks for watching & subscribe to my channel & share my channel with your friends .Give me your suggestion to improve ourselves and encourage us to prepare more videos.
Thanks & Regards.
I VSR TECH I
Повторяем попытку...
Доступные форматы для скачивания:
Скачать видео
-
Информация по загрузке: