Power Transformer Protection Philosophy Explained | Differential, REF, OC & EF Backup Logic
Автор: ELECTRICAL FUNDAZ
Загружено: 2026-01-31
Просмотров: 77
Описание:
🔗 LinkedIn Post
https://www.linkedin.com/posts/nitinn...
00:00 Introduction
01:05 Why Transformer Protection Needs Multiple Layers
02:10 Thermal Protection – WTI & OTI
04:00 Differential Protection (87T)
05:40 Restricted Earth Fault (REF)
07:00 Buchholz & PRV – Incipient Faults
08:30 Harmonic Blocking Explained
09:30 LV Backup OC & EF
11:10 HV Backup OC & EF
12:40 Feeder Protection Coordination
14:00 Most Important Fault Escalation Logic
16:00 Parallel vs Independent Transformer Philosophy
17:30 Final Summary
Power transformer protection is not just about relays — it’s about selectivity, coordination, and guaranteed fault clearance.
In this video, I explain the complete power transformer protection philosophy using a single, easy-to-understand diagram. The discussion covers thermal protection, main protection, mechanical protection, backup OC & EF protection, and most importantly, how protection escalates when downstream protection fails.
🔍 Topics Covered in This Video:
Thermal protection using WTI & OTI
Transformer Differential Protection (87T)
Restricted Earth Fault (REF – 64)
Buchholz & PRV for incipient faults
2nd & 5th harmonic blocking
LV & HV backup OC & EF protection
Feeder protection coordination
Step-by-step fault escalation logic
Directional vs non-directional LV backup philosophy
Parallel vs independent transformer operation
This video is especially useful for:
Protection & testing engineers
Substation engineers
Power system students
Utility and transmission professionals
⚠️ Most Important Protection Philosophy Explained
✔ Feeder fault → Feeder protection operates first
✔ If feeder protection fails → LV backup operates
✔ If LV backup fails → HV backup operates
✔ If HV backup fails → Remote-end protection clears the fault
✔ Internal transformer fault → Differential protection (87T) operates first
✔ If differential fails → HV backup protection operates
✔ LV backup is Non-directional for independent transformers
✔ LV backup is Directional (towards HV) for parallel transformers
This philosophy ensures selectivity first, backup always, and fault clearance under all conditions.
#PowerTransformer
#TransformerProtection
#DifferentialProtection
#REFProtection
#OC_EF
#PowerSystemProtection
#SubstationEngineering
#ElectricalEngineering
#ProtectionRelay
#Mahatransco
#EHVSubstation
#TestingAndCommissioning